Secutron MR-2308-LR Panneau de contrôle d’alarme incendie conventionnel 8 zones
MR-2308-LR
|5T-MR2308LR
Acheter Secutron
Secutron MR-2308-LR Panneau de contrôle d’alarme incendie conventionnel 8 zones
MR-2308-LR | 5T-MR2308LR
Veuillez vous connecter pour voir les tarifs, consulter la disponibilité des produits et ajouter des articles à votre panier.
Aperçu
Spécifications
Documents
Aperçu
The MR-2308-LR and MR-2308-LDR are equipped with eight Class "B" (Style "B") initiating circuits and four Class "B" (Style "Y") indicating circuits rated at 1.7A maximum. (Total of 5A) The MR-2308-LDR is equipped with a built-in UDACT/Digital Communicator. Two MR-2300-A Six Initiating Circuit Class "A" Converter Modules may be used for Class "A" (Style "D") wiring of the initiating circuits. One MR-2300-NC4 Four Indicating Circuit Class "A" Converter Module may be used for Class "A" (Style "Z") wiring of the indicating circuits. The MR-2308-LR and MR-2308-LDR are configurable by the keypad (using the CFG-300 Configuration Tool) for onsite programming or by a PC for both onsite and remote programming. The cabinet will support up to 12AH batteries. The panels can be semi-flush mounted with the optional MR-2312-FT trim ring.
Principales caractéristiques
- Listed to UL 864, 10th edition and ULC S527 Ed 4
- Available in eight and twelve zone configurations with an integrated UDACT/Digital Communicator on select models
- Front panel (using CFG-300 configuration tool) and PC programmable
- Remote upload/download capabilities
- Base panel is equipped with Class “B” (Style “B”) initiating circuits which may be configured as Class “A” (Style “D”) using a Class “A” converter module
- Initiating circuits may be configured as Alarm, Verified Alarm, Waterflow Alarm, Sprinkler Alarm, Latching or Non-Latching Supervisory, Monitor and Trouble-Only
- Base panel is equipped with Class “B” (Style “B”) indicating circuits which may be configured as Class “A” (Style “Z”) using a Class “A” signal converter module
- Individual disconnect buttons for both initiating and indicating circuits
- Audible signals may be configured for Steady, Temporal Code, California Code and March Time
- Indicating Circuits may be configured as Silenceable or NonSilenceable for both signals and strobes
Renseignements généraux
Name: Secutron MR-2308-LR 8 Zone Conventional Fire Alarm Control Panel
Category: Secutron, Fire, Fire Control Panels, Fire Alarm Control Panels
UPC Code: 778346007068
Country of Origin: Canada. Country of origin is subject to change.
Spécifications
ADI Numéro du produit 5T-MR2308LR Code fabricant MR-2308-LR Marque Secutron